RWD CONTROLLER’S

  RWD CONTROLLER’S


The RWD family of Universal Controllers are intended for heating, air conditioning, ventilation and refrigeration in comfort control applications.


OUR WORKS( HUMIDIFICATION PLANT AUTO CONTROL)Based on the Department Relative Humidity the pump & Fan are ON/OFF Automatically.Single pump(Fan ON/OFF) Control.TWO pump(Fan ON/OFF) Control.



TYPES



        •RWD 32   RWD 62    RWD 68   RWD 82   RWD 62U   RWD 68URWD 82U RWD 44U  RWD 60Ect…….

        

        •RLU 220   RLU 222  RLU 232  RLU 210  RWG 1.M12D   RMS 705RMS 760 B  SHE 62.1  SEM 62.2Ect…….

RWD controllers and other types of controllers



APPLICATIONS

RWD62U/68U/82U main loop control applications are designed for temperature, static pressure, humidity, air pressure, fluid pressure, refrigeration, air quality and air fluid velocity control. The controller contains pre-programmed applications.


The universal RWD32/RWD82/RWD68 controllers are used for comfort control in HVAC systems.


Two digital outputs selectable between 2 stages of on/off control or as a single 3 point controller.


The main analogue input can be set as °C, °F, % or no specified unit.



INPUTS & OUTPUTS PORTS

Module
Operatig  Voltage
        Outputs
Digital Port
Analog  Port
(0 to10 V dc)
    Input                    Output
RWD62U
24 V ac
      –
      2              2
RWD68U
24 V ac
      1
      2              1
RWD82U
24 V ac
      2
      2              -
RWD44U
24 V ac
      4
      2              -
RWD45U
24 V ac
      1
      3
RWD 32
230 V ac
      2
      2              -
RWD 82
24 V ac
      2
      2              -
RWD 68
24 V ac
      1
      2              1


GENERAL SPECIFICATIONS

  Power Supply

Operating voltage ....24 V ac + 20%
Frequency ....50/60 Hz
Power Consumption ....3.5 VA

  Set Point
Adjustment Range...-58°F to +302°F (-50°C to +150°C)


Display Resolution (Does Not Relate to Controller Accuracy)
Siemens Ni 1000 Ohm....1°F (0.5°C)
Pt 1000 Ohm ....1°F (0.5°C)
Active Sensor ...Depends on Setting Range


RWD62U/68U/82U
Digital Input D1
Polling Voltage for Control Commands (D...M) ....15 Vdc
Current Consumption.....<15 mA
       
RWD68U
Analog Outputs Y1, Y2
Range ....0 to 10 V dc
Maximum Current....+1 mA
Digital Output (Q1)
Relay Contacts (potential-free)
Voltage ....24 V ac to 230 V ac
6A Res/5A Ind/5 FLA/ 30 LRA/ 1/2 HP 30 V dc, 4A
  
RWD82U
Digital Outputs ....Q1, Q2
Relay Contacts (potential-free)
Voltage ....24 Vac to 230 Vac
6A Res/5A Ind/5 FLA/ 30 LRA/ 1/2 HP 30 Vdc, 4A 

  Environmental Conditions  Temperature....32°F to 122°F (0°C to 50°C)
Humidity ....<95% RH




G, G0   24 V ac supply ( SELV AC 24 V Power supply)L-N   AC 230 V supplyD1   Digital inputM   Ground (G0) for signal inputs
Q1-Q4   Relay outputs; various voltages permissiblex1   Signal input (Main Input: Siemens Ni 1000, Pt   1000 and 0-10 V dc)x2   Signal input (Aux. Input: Siemens Ni 1000, Pt   1000 and 0-10 V dc)x3   Signal input (Eco. Sensor or second ind. Input: Siemens Ni 1000, Pt 1000 and 0-10 V dc)Y1   Analog output (0 to 10 V dc)Tool   Communication port with PC (9 pin plug)Note  M, GND and G0 are internally connected.



OUR PROJECTS SAMPLE IMAGES 






THANK YOU

If Any Query's Please Contact Our Mail id 



Comments

Post a Comment

Popular posts from this blog

SIEMENS DUCT SENSORS