RWD CONTROLLER’S
RWD CONTROLLER’S
•Operating
voltage ....24 V ac + 20%
• Set Point
•Display Resolution (Does Not Relate to Controller Accuracy)
• Environmental Conditions •Temperature....32°F
to 122°F (0°C to 50°C)
•G,
G0 24 V
ac supply ( SELV AC 24 V Power supply)•L-N AC 230 V supply•D1
Digital
input•M
Ground
(G0) for signal inputs
•The RWD family of Universal Controllers are intended for heating, air conditioning, ventilation and refrigeration in comfort control applications.
•OUR WORKS( HUMIDIFICATION PLANT AUTO CONTROL)•Based on the Department Relative Humidity the pump & Fan are ON/OFF Automatically.•Single pump(Fan ON/OFF) Control.•TWO pump(Fan ON/OFF) Control.
TYPES
•RWD 32 •RWD 62 •RWD 68 •RWD 82 •RWD 62U •RWD 68U•RWD 82U •RWD 44U •RWD 60•Ect…….
•RLU 220 •RLU 222 •RLU 232 •RLU 210 •RWG 1.M12D •RMS 705•RMS 760 B •SHE 62.1 •SEM 62.2•Ect…….
•RWD controllers and other types of controllers
•RWD62U/68U/82U main loop control applications are designed for temperature, static pressure, humidity, air pressure, fluid pressure, refrigeration, air quality and air fluid velocity control. The controller contains pre-programmed applications.
•The universal RWD32/RWD82/RWD68
controllers are used for comfort control in HVAC systems.
•Two digital outputs selectable between 2
stages of on/off control or as a single 3 point controller.
•The main analogue input can be set as °C,
°F, % or no specified unit.
Module
|
Operatig Voltage
|
Outputs
|
|
|
|
Digital
Port
|
Analog
Port
(0
to10 V dc)
Input Output
|
RWD62U
|
24
V ac
|
–
|
2 2
|
RWD68U
|
24
V ac
|
1
|
2 1
|
RWD82U
|
24
V ac
|
2
|
2 -
|
RWD44U
|
24
V ac
|
4
|
2 -
|
RWD45U
|
24
V ac
|
1
|
3
|
RWD
32
|
230
V ac
|
2
|
2 -
|
RWD
82
|
24
V ac
|
2
|
2 -
|
RWD
68
|
24
V ac
|
1
|
2 1
|
GENERAL SPECIFICATIONS
• Power Supply
•Operating
voltage ....24 V ac + 20%
•Frequency
....50/60 Hz
•Power
Consumption ....3.5 VA
• Set Point
•Adjustment
Range...-58°F to +302°F (-50°C to +150°C)
•Display Resolution (Does Not Relate to Controller Accuracy)
•Siemens
Ni 1000 Ohm....1°F (0.5°C)
•Pt
1000 Ohm ....1°F (0.5°C)
•Active
Sensor ...Depends on Setting Range
RWD62U/68U/82U
Digital Input D1
Polling Voltage for Control Commands
(D...M) ....15 Vdc
Current Consumption.....<15 mA
RWD68U
Analog Outputs Y1, Y2
Range ....0 to 10 V dc
Maximum Current....+1 mA
Digital Output (Q1)
Relay Contacts (potential-free)
Voltage ....24 V ac to
230 V
ac
6A Res/5A Ind/5 FLA/ 30 LRA/ 1/2 HP 30 V
dc,
4A
RWD82U
Digital Outputs ....Q1,
Q2
Relay Contacts (potential-free)
Voltage ....24 Vac to
230 Vac
6A
Res/5A Ind/5 FLA/ 30 LRA/ 1/2 HP 30 Vdc, 4A
• Environmental Conditions •Temperature....32°F
to 122°F (0°C to 50°C)
•Humidity
....<95% RH
•G,
G0 24 V
ac supply ( SELV AC 24 V Power supply)•L-N AC 230 V supply•D1
Digital
input•M
Ground
(G0) for signal inputs
•Q1-Q4
Relay
outputs; various voltages permissible•x1
Signal
input (Main Input: Siemens Ni 1000, Pt 1000
and 0-10 V dc)•x2
Signal
input (Aux. Input: Siemens Ni 1000, Pt 1000
and 0-10 V dc)•x3
Signal
input (Eco. Sensor or second ind. Input: Siemens Ni 1000, Pt 1000 and 0-10 V
dc)•Y1
Analog
output (0 to 10 V dc)•Tool
Communication
port with PC (9 pin plug)•Note M, GND and G0 are internally connected.
OUR PROJECTS SAMPLE IMAGES
THANK YOU
Good System..
ReplyDelete